Venstar T1050 Owner's Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
About Advanced Features & Operation
DEADBAND OPERATION - Controls up to two Heat and two Cool stages
(please see the diagram on the next page).
And
The 2nd Stage of heat or cool is turned on when:
(A) The 1st Stage has been on for a minimum of two minutes.
(B) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #6, page 12),
plus the 2nd stage deadband. This 2nd stage deadband is fixed at
two degrees and is not adjustable.
The 1st Stage of heat or cool is turned on when:
(A) The temperature spread from the setpoint is equal to or greater
than: the setpoint plus the 1st stage deadband (step #6, page 12).
This 1st stage deadband is adjustable from 1-6 degrees and the
default is two degrees.
Page 15
CALIBRATION - Under normal circumstances it will not be necessary to
adjust the calibration of the temperature. If calibration is required,
please contact a trained HVAC technician to correctly perform the
following procedure.
Place the therm-
ostat in the OFF
mode.
Press
MODE button.
While holding the
MODE button,
press and hold the
DOWN button for
5 seconds. All icons
will appear on the display.
and hold the
MODE
Press the MODE
button once. The
thermostat temp-
erature will be
displayed and
may be calibrated
using the UP or DOWN buttons.
After calibration is
complete, press
the MODE button
once to save
your changes and
return to normal operation.
MODE
MODE
OFF
o
Pm
I2:00
Mo
88
88
HEAT
COOL
ONOFF
AUTO
Fan On
Program
Locked
Setup
On
o
Am
Pm
I8:88
Day
Night
Evening
Morning
SuMoTuWeThFrSa
OFF
o
Pm
I2:00
Mo
o
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20

Comments to this Manuals

No comments