Submittal Coversheet
Project Name
DPS Moore k-8 General Renovation
DPS Project Number
PP2218
Date
6/17/2014
Architect
2000 South Colorado Blvd Tower One Suite 6000 Denver, CO 80222
Contractor
GH Phipps
5995 Greenwood Plaza Blvd. Suite 100 Greenwood Village, CO 80111
Subcontractor/Prepared by.
Walrath
7935 West 14th Ave Lakewood, CO 80215
Supplier
Manufacturer
Carrier
Submittal Number
235400.01
Specification Section
235400
Drawing Number/Location
MDF 001A
Contractor Review
AHU-1 CU-1
Architect/Engineer Review
THIS SUBMITTAL REVIEW IS FOR GENERAL COMPLIANCE WITH THE DESIGN CONCEPT OF
THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE
CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF
THE PLANS AND SPECIFICATIONS. THE CONTRACTOR IS RESPONSIBLE FOR ALL
QUANTITIES, DIMENSIONS (WHICH ARE TO BE CORRELATED AT THE JOB SITE),
FABRICATION PROCESSES, MEANS, METHODS AND TECHNIQUES OF CONSTRUCTION,
COORDINATION OF THE WORK WITH THAT OF OTHER TRADES, AND THE SATISFACTORY
PERFORMANCE OF THE WORK IN A SAFE AND SATISFACTORY MANNER.
NET
NO EXCEPTIONS TAKEN
AOAN
APPROVED ONLY AS NOTED
(PROVIDE CONFIRMATION OF COMPLAINCE)
R
REJECTED
RR
REVISE AND RESUBMIT
SSI
SUBMIT SPECIFIED ITEM
Contractor to coordinate
RA/Filter plenum as noted on
plans for a vertical installation
with a bottom return air inlet.
Provide TXV as required per
manufacturer.
Digitally signed by Kristin Blundell
DN: C=US,
O=The CE Group, CN=Kristin
Blundell
Date: 2014.06.18 11:05:00-06'00'
Page view 0
1 2 3 4 5 6 ... 36 37

Summary of Contents

Page 1 - Submittal Coversheet

Submittal CoversheetProject NameDPS Moore k-8 General RenovationDPS Project NumberPP2218Date6/17/2014ArchitectShort Elliot Hendrickson2000 South Color

Page 2 - SUBMITTAL COVER SHEET

Certified Drawing for AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert Bernal5 DIMENSIONS(cont.) A12508Fig. 2 -- FB4CNP --Englis

Page 3

Electrical Disconnect SUBMITTAL Tag: AHU-1 Model #: DFADK0201DSC Qty: 1 Revision Date: 06/16

Page 4 - AHU-1 CU-1

NOTE: Read the entire instruction manual before starting the installation.This symbol → indicates a change since the last issue.SAFETY CONSIDERATIONSI

Page 5 - Unit Report For AHU-1 CU-1

9. Cut insulation away from rectangular access hole in blower access panel.10. Remove adhesive backing from window bezel. From the outside of the door

Page 6 - Electrical Data

Fig. 2—Wiring ConnectionsA00001NOTE: Route wires as shownGROUNDLOADLINEPULL TODISCONNECTFig. 3—Installation of BezelA03064ADHESIVEWINDOW BEZELPRIOR TO

Page 7 - Acoustic Summary

Condensate Pump SUBMITTAL Tag: AHU-1 Model #: VCMA15ULS Electrical: 115 Volt - 60 Hertz Qty: 1 Revision Dat

Page 8

Wastewater • Water Systems • HVAC • Industrial • Engineered Products •1/2 gallon collection tank •Vertical centrifugal pump design •Automatic s

Page 9 - Fig. 1 -- FB4CNF -- English

Engineering DataSpecications Replacement PartsItem Part NumberTank 154401Cover, motor 154421Float arm 154452Switch holder 154471Switch 950337Check va

Page 10 - Fig. 2 -- FB4CNP --English

Thermostat and Sensor SUBMITTAL Tag: AHU-1 Model #: T2900/ACC0400 Qty: 1 ea. Revision Date: 06/16/14 4800 O

Page 11 - .LOHMILLER.COM

Venstar Programmable Thermostat T2900STANDARD FEATURES: • Up to 3-Occupied, 1-Unoccupied periods per day, with copy command for easy programming• Ligh

Page 12 - Installation Instructions

SUBMITTAL COVER SHEET JOB: DPS – Dora Moore LOCATION: Denver, CO CONTRACTOR: Walrath ENGINEER: The CE Group EQUIPMENT TAG QTY MODEL NUMBER

Page 13

models: ACC0401, TB400, ACC0400, & ACC0435 wired sensorsaccessories © Venstar Inc. 88-6544.08Model ACC0401The remote indoor temperature sensor

Page 14 - Fig. 3—Installation of Bezel

Low Ambient, Evap Freeze T-stat, Time-Delay Relay, Winter Start Control, Wind Baffle, Crankcase Heater SUBMITTAL Tag: CU-1 Model #: 53

Page 15

15 3 D S --- 9 0 0 --- --- --- 0 8 65 3 D S --- 9 0 0 --- --- --- 0 9 5Installation InstructionsDu ct---F ree Sys temsCoo ling Only and Heat Pump Unit

Page 16 - VCMA-15 Series

2Winter Start Control (part number KAAWS0101AAA) isrequired when low ambient operation (cooling below 55_F/13_C)is required for cooling and heat pump

Page 17 - Performance Data

3COOLING ONLY MODELSModel No. Wire Color38MVC009---024Black = 009 & 012Red = 018 & 02438HDF018---036 Black38HDR018--- 060 Black538A Series Bla

Page 18

4CHECK OPERATIONBefore starting the system to check operation of low ambienttemperature control, ensure that the power wiring and location ofcontrol a

Page 19 - ENGINEER:

NOTE: Read the entire instruction manual before starting the installation.This symbol → indicates a change since the last issue.INTRODUCTIONThis instr

Page 20 - ACC0400, & ACC0435

6. Mount electrical box to plenum or casing using 2 No. 10-24 X 1/2-in. sheet metal screws. (See Fig. 1.)7. Mount evaporator freeze thermostat to side

Page 21

KAATD0101TDRInstallation InstructionsTIME- - DELAYRELAY KITNOTE: Read the entire instruction before beginning theinstallation.INTRODUCTIONThe Time-- D

Page 22

2FAN-COIL OR FURNACE LOW-VOLTAGE TERMINAL BOARDFIELD CONNECTIONSBRNBLKORNREDRGGYWCFROM ONTHERMOSTATFANTIME-DELAY2 15/16″1 15/16″ 1/ 8 IN. DIA(2)

Page 23 - INSTALLATION

Fan Coil and Air Conditioner SUBMITTAL Tag: AHU-1, CU-1 Model #: FB4CNF/38HDR Electrical: 208/230 Volt - 1 Phase – 60 Hertz Qty: 1 ea.

Page 24 - 53DS-- 900-- -- -- 086, 095

KAAWS0101AAAInstallation InstructionWinter Start ControlNOTE: Read the entire instruction manual before starting theinstallation.SAFETY CONSIDERATIONS

Page 25 - CHECK OPERATION

2WireContactBaseWireStopBlueTapWirePlastic FlangeA07934LPSRunWireYellow w/ RedBlue TapWireA07944Fig. 1 -- Installation(Y) (C)T1 T2CT3LPS24 VAC24 VACLP

Page 26

5 3 D S --- 9 0 0 --- --- --- 0 7 05 3 D S --- 9 0 0 --- --- --- 0 7 15 3 D S --- 9 0 0 --- --- --- 0 8 75 3 D S --- 9 0 0 --- --- --- 0 8 8Installati

Page 27

2Table 1—Kit Contents and UsageWind Baffle Kit Part No. Usage Kit Contents*5 3 D S --- 9 0 0 --- --- --- 0 7 038HDF01838HDR01838QRF01838QRR018538ENF01

Page 28

KAACH1201KAACH1301KAACH1401KAACH1501KAACH1601KAACH1701KAACH1801Installation InstructionsCrankcase Heater KitKAACH1901KAACH2001KAACH2101KAACH2201KAACH2

Page 29 - Catalog No: AG--KAATD--02

2POWER LEADSHEATER FASTENINGCLIPCRANKCASEHEATERCOMPRESSOR2”(50.8 mm)A90297Fig. 1 -- Crankcase Heater Installation2111BLKBLKCRANKCASE HTRA06075Fig. 2 -

Page 30 - Installation Instruction

3A11630Fig. 5 -- Control Board(for kit numbers 2201, 2301 and 2401)

Page 31 - T3 = 24 VAC Com

4Copyright 2012 CAC / BDP S 7310 W. Morris St. S Indianapolis, IN 46231Manufacturer reserves the right to change, at any time, specifications and desi

Page 32

Table Of Contents AHU-1 CU-1 Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert BernalUnit Report 2Performance Summary 3Acoustic Summary

Page 33

Unit Report For AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert BernalUnit ReportOutdoor Unit Parameters Unit Model:38HDR

Page 34

Performance Summary For AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert BernalPerformance SummarySystem PerformanceSystem: 38HD

Page 35 - CRANKCASE HTR

Acoustic Summary For AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert BernalAcoustic SummaryOutdoor Unit Parameters: Unit Mod

Page 36 - Fig. 5 -- Control Board

Certified Drawing for AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert BernalCertified Drawing8 DIM ENS I ONS - - ENGLI S H H G

Page 37 - Catalog No: IIK--KAACH--09

Certified Drawing for AHU-1 CU-1Project: DPS - Dora Moore K-8 06/16/2014 Prepared By: Robert Bernal4 DIMENSIONSA12512Fig. 1 -- FB4CNF -- English Page

Comments to this Manuals